Ultra-low residual voltage arresters for rotating machine protection — 3–20 kV
Specially designed for rotating machines — generator stator windings and large motor terminals have significantly lower impulse withstand (BIL) than static equipment. Standard distribution arresters won’t protect them adequately. These arresters deliver ultra-low residual voltage specifically matched to rotating machine insulation levels.
Installed at the power plant busbar or feeder side — the first line of defence before surges reach the generator. HY5WZ-17/45 = HY Polymer ZnO · 5 5 kA · W Gapless · Z Station/Plant type · 17 Rated kV · 45 Lightning residual ≤kV.
| Model | Sys. kV | Ur kV | Uc kV | DC 1mA ≥kV | Lightning ≤kV | Switching ≤kV | Steep ≤kV | 2ms A |
|---|---|---|---|---|---|---|---|---|
| HY5WZ-5/13.5 | 3 | 5 | 4.0 | 7.5 | 13.5 | 11.5 | 15.5 | 150 |
| HY5WZ-10/27 | 6 | 10 | 8.0 | 15.0 | 27.0 | 23.0 | 31.0 | 150 |
| HY5WZ-17/45 | 10 | 17 | 13.6 | 24.0 | 45.0 | 38.3 | 51.8 | 150 |
| HY5WZ-51/134 | 35 | 51 | 40.8 | 73.0 | 134 | 114 | 154 | 400 |
| HY5WZ-84/221 | 66 | 84 | 67.2 | 121 | 221 | 188 | 254 | 400 |
| HY5WZ-90/235 | 66 | 90 | 72.5 | 130 | 235 | 201 | 270 | 600 |
Mounted directly at the generator or large motor terminals — the last line of defence, right where the rotating machine connects. Ultra-low residual voltage because generator winding BIL is the most sensitive in the power system. HY5WD-13.5/31 protects a 10.5 kV generator with lightning residual ≤31 kV.
| Model | Generator kV | Ur kV | Lightning ≤kV | Application Example |
|---|---|---|---|---|
| HY5WD-4(3.8)/9.5 | 3.15 | 4 (3.8) | 9.5 | Small hydro generators, 3.15 kV |
| HY5WD-8(7.6)/18.7 | 6.3 | 8 (7.6) | 18.7 | Industrial motors, 6.3 kV |
| HY5WD-13.5(12.7)/31 | 10.5 | 13.5 (12.7) | 31 | Thermal power generators, 10.5 kV |
| HY5WD-20/45 | 15.75 | 20 | 45 | Large generators, 15.75 kV |
| HY5WD-23/51 | 18 | 23 | 51 | Gas turbine generators, 18 kV |
| HY5WD-25/56.2 | 20 | 25 | 56.2 | Large steam turbine, 20 kV |
| The Problem | Generator stator winding BIL (Basic Impulse Insulation Level) is typically only 1.25× the rated voltage — much lower than the 3–4× margin that transformers and switchgear are designed to. A 10.5 kV generator may have a BIL of only ~30 kV. A standard YH5W-12 arrester has a residual voltage of 36 kV — too high to protect the winding. |
|---|---|
| The Solution | Generator-class arresters use specially selected ZnO blocks with a steeper non-linear curve at low currents — producing a residual voltage up to 30% lower than standard distribution arresters at the same rated voltage. This brings the protection level below the generator’s actual BIL. |
| HY5WZ vs HY5WD | HY5WZ — bus/feeder side: broader voltage range (3–110 kV), moderate residual reduction. HY5WD — direct terminal: generator voltage only (3–20 kV), maximum residual reduction, closest to the machine. |
| Associated Standard | JB/T 8952 (Chinese standard for gapless metal oxide arresters for AC power systems). IEC 60099-4 testing adapted for lower residual voltage verification. |
HY5WZ at the generator busbar, HY5WD at each generator terminal — layered protection for the most expensive rotating asset in a power station.
HY5WD directly at motor terminals for critical drives — pumps, compressors, fans in refineries, steel mills and mining operations where motor downtime costs exceed the motor itself.
HY5WZ on the low-voltage side of GSU transformers — the interface between generator and transformer where reflected waves from HV switching can damage the LV winding.
Compact HY5WD arresters integrated in wind turbine nacelle switchgear — protecting the generator from lightning surges via the blade and tower.
Tell us your machine’s voltage, power rating and earthing type — we’ll recommend the right arrester.